Fixed ladder planner. Clearer access decisions.
Explore fixed rung ladders, roof transitions and landing requirements. Build a clear brief for your designer and installer.
Use the interactive tools to plan an arrangement, check a landing, read requirements and prepare an installation review. Confirm the worksite state; NSW is selected by default. These are preliminary references requiring site-specific design and competent review.
Fixed ladder design FAQs
When is a rest platform or intermediate landing required?
For the normal AS 1657:2018 arrangement, Clause 7.3.6 limits vertical spacing between landings to 6 m. Clause 7.4.6 applies these provisions to twin-stile rung ladders. Plan intermediate landings when the total vertical rise exceeds this interval.
- Total access height can exceed 6 m by using multiple flights with intermediate landings.
- Successive ladders must change direction by 180° or be staggered. If neither is possible, the clause requires other protection against a fall exceeding 6 m, such as a barrier or a landing at least 1.5 m long. Staggered ladders require at least 700 mm between centre-lines.
- Closer spacing can be required by the governing design, manufacturer or asset authority. Appendix H is informative; its steep-ladder guidance must be distinguished from a mandatory project requirement.
Layout options within the clause: For successive flights above 6 m, use the required direction change or stagger. If neither can be provided, the clause requires another means of limiting the fall to 6 m, with examples including a barrier or a landing at least 1.5 m long. This is a qualified fall-path provision, not permission to omit every landing.
References: AS 1657:2018, cls. 7.3.6 & 7.4.6
How are longer climbs divided into flights?
Under the normal 6 m arrangement, a 6.9 m total rise divides into two equal 3.45 m flights with one intermediate landing. A 9 m total rise divides into two 4.5 m flights with one intermediate landing. End landings are additional.
- Select the landing arrangement and fall protection together; fitting a cage or line does not change the normal landing interval.
- Use the matching multi-flight manufacturer system, with designed landings, direction changes, fixings, protection and end transitions.
- Kattsafe publishes a 6 m maximum distance between rest platforms for its RL30/RL40/RL50 references. Any proposed departure requires the separate assessment described below.
References: AS 1657:2018, cl. 7.3.6; Kattsafe product range
Kattsafe rung-ladder range and specifications · AS 1657:2018 — publisher and full standard
Can a landing be omitted if it is not reasonably practicable? Is there another maximum height?
Clause 7.3.6 Note 3 specifically contemplates situations where intermediate landings are not reasonably practicable and recommends an AS/NZS 1891-series fall-arrest system. It is a recommendation associated with the clause, not a general numeric extension of its normal limit.
- Note 3 states no alternative numeric maximum. It does not authorise unlimited height or establish a cage-only exception.
- Any acceptable alternative depends on the governing law/specification, a documented assessment and the exact product design. A risk assessment or an engineer's opinion cannot by itself waive binding requirements.
- For a Kattsafe system, obtain written manufacturer consent for any departure from its installation guide. Without the required evidence and acceptance, retain a documented landing arrangement or select another suitable access method.
- The note gives examples including lighting/transmission towers, wind-turbine towers and pits. Being a tower or having limited space does not itself establish that the conditions are met. No special uninterrupted-climb design is generated here.
Conditional note — not an automatic approval: Note 3 addresses landings that are not reasonably practicable and recommends conforming fall arrest. Demonstrate the actual constraint, assess safer access/layout options, verify the product and structural design, and establish the permitted basis and required acceptance. It sets no alternative numeric maximum. Retain a documented landing arrangement if that basis cannot be established.
References: AS 1657:2018, cl. 7.3.6 Note 3; Kattsafe manual p. 9
Kattsafe rung-ladder installation manual (PDF) · AS 1657:2018 — publisher and full standard
Which requirements are mandatory, and which are guidance?
Within a standard, 'shall' expresses a requirement and 'should' expresses a recommendation. This distinction does not itself determine which legislation, edition, contract or asset specification governs your site.
- Standards Australia publishes voluntary standards, which may become mandatory through legislation. A contract or asset specification may also require compliance.
- A note recommending fall arrest is not equivalent to a clause granting an unrestricted exemption.
- Read the standard's own conventions: AS 1657's preface says mandatory statements in notes to figures are requirements. It identifies informative appendices and commentary as guidance rather than clauses. Do not treat every item labelled 'note' as having the same effect.
- A workplace code has a different legal context from a voluntary standard. In NSW, SafeWork explains that the duty from 1 July 2026 requires compliance with relevant codes or an equivalent-or-higher method of managing the risk. Its explanation of 'should' in a code is not the same as reading a recommendation in AS 1657.
- Identify the governing requirements and record whether the final arrangement meets the prescriptive provisions, follows a permitted alternative, or retains a departure/non-conformance. A webpage or checked box does not certify any of these outcomes.
References: Standards Australia: standards and legal status; AS 1657:2018 preface; SafeWork NSW codes guidance
Standards Australia — standards status and access · AS 1657:2018 — publisher and full standard · SafeWork NSW — current code duty and terminology
When is a fixed ladder required, rather than stairs or another access method?
There is no universal building-height trigger in this planner that makes a fixed ladder the required answer. Select safe access for the actual operating, inspection and maintenance tasks, frequency, tools, users and site constraints.
- Assess work from ground/solid construction, stairs and walkways before relying on a ladder or harness system.
- A ladder can restrict carrying tools and casualty recovery. Routine access may justify an easier access method.
- These rung-ladder references are not designs for normal building egress, portable ladders, step-type ladders or evacuation.
References: AS 1657:2018, cl. 2.2; SafeWork NSW: working at heights
SafeWork NSW — working at heights · AS 1657:2018 — publisher and full standard
At what height are cages and fall-arrest lines needed?
Landing spacing and fall protection are separate. For twin-stile rung ladders, Clause 7.4.7 requires a cage for potential falls exceeding 6 m, independently of landing locations; it requires AS/NZS 1891-series fall arrest where a cage cannot be installed. Note 2 recommends considering a cage below 6 m.
- Use potential fall distance, including a possible fall past a lower landing, rather than just the access height.
- Kattsafe's rung-ladder manual prefers an enclosed cage above 3.5 m. This manufacturer recommendation is not a universal statutory 3.5 m trigger.
- A cage does not arrest a fall. Steep/vertical ladders require specific review of the applicable falls code, suitable fall-arrest equipment and rescue; the selected state's guidance is linked above.
- Single-stile ladders have separate provisions: Clause 7.5.1 requires fall arrest above 3.5 m potential fall distance. Do not apply this planner's twin-stile configuration to that ladder type.
- If the potential fall is 6 m or less, Clause 7.4.7's over-6 m trigger is not engaged, but Note 2, the manufacturer, the actual hazards and the applicable workplace rules can still call for protection. 'Below the trigger' is not a finding that an exposed ladder is safe.
- If the potential fall is over 6 m and a cage can be installed, use the clause's cage provision together with all other applicable requirements. If a cage cannot be installed, the clause requires the conforming fall-arrest alternative. This condition is different from Note 3's test for intermediate landings that are not reasonably practicable.
- A fall-arrest selection needs the exact compatible device, harness, transfer arrangements, structure, fall clearance, user training and effective rescue. Do not assume that a line can be fitted to an ordinary or suspended ladder without verifying the resulting loads and manufacturer consent.
- For multiple flights, assess the route past the landings as well as each flight. A landing may reduce a possible fall only when its actual layout, guarding and change of direction or stagger provide the intended protection. The diagram cannot determine that for an existing site.
Express conditional alternative — where a cage cannot be installed: Clause 7.4.7 provides the AS/NZS 1891-series fall-arrest alternative in that circumstance. It is separate from the landing-impracticability note and does not approve a generic cable, a manufacturer departure or a different landing interval. Document the exact condition and verify the complete system before relying on it.
References: AS 1657:2018, cl. 7.4.7; Kattsafe manual p. 10; SL228 guide; AS/NZS 1891.4:2025
Kattsafe rung-ladder installation manual (PDF) · AS 1657:2018 — publisher and full standard · Standards Australia — AS/NZS 1891.4:2025 · Kattsafe SL228 vertical fall-arrest guide (PDF)
Is a separate platform always required at the top or bottom?
A safe landing and transition must be provided. A separate prefabricated platform is not automatically necessary when an existing suitable surface already serves as the landing. Kattsafe's manual requires base/top landings when the entry/exit surface is uneven or not level.
- Check the existing floor/roof's strength, level, slip resistance, standing space, guarding and safe route beyond the ladder.
- Pitched roofs, parapets and hatches need their matching manufacturer access detail. Do not assume a roof edge or an open hatch is a safe landing.
- Normal landing checks include 900 mm minimum length from the face of the lowest rung, width at least the ladder width or 600 mm (whichever is greater), 2000 mm headroom and 600 mm clear standing space. Loading, guarding and other geometry remain to be checked.
- An intermediate rest landing, a top access platform and a rung/footrest perform different functions. A footrest is not automatically a compliant intermediate landing.
- Clause 7.4.3.5 permits up to 7° total cross-slope at the bottom landing, subject to the prescribed rung relationship. This limited allowance does not override the exact product instructions or approve a general pitched-roof transition.
References: AS 1657:2018, cls. 7.3.6, 7.4.3.5 & 7.4.8; Kattsafe manual p. 10
Kattsafe rung-ladder installation manual (PDF) · AS 1657:2018 — publisher and full standard
How does ladder angle affect the design?
AS 1657 distinguishes step-type ladders from twin-stile rung ladders. The rung-ladder range is 70°–90°, with 70°–75° preferred; step-type ladders use a different 60°–70° range. Kattsafe's illustrated references here use 75° angled or 90° vertical configurations.
- For the same vertical rise, a shallower angle increases both climbing length and horizontal projection. A vertical ladder has no geometric horizontal projection, but still needs its specified clearances.
- A different angle changes brackets, cage geometry, transitions and fall-protection considerations. The planner withholds a configuration illustration when the angle differs from its documented reference.
- The rung count shown is an approximate number of spaces along the ladder at the published 300 mm pitch, not a manufacturing or cut/drill schedule.
References: AS 1657:2018, cl. 2.2, Figure 2.1 & cl. 7.4.1; Kattsafe manual p. 10
Kattsafe rung-ladder installation manual (PDF) · AS 1657:2018 — publisher and full standard
What can this page actually confirm?
It can calculate preliminary geometry, compare entered landing dimensions with stated reference minima and organise an evidence log. It cannot confirm an installed system's compliance, approve an exception, check structural capacity or replace the manufacturer's drawings and a competent assessment.
- Installation, inspection and final handover need the exact product instructions, site measurements and required competent sign-off.
- Do not use a system with defects or unresolved safety concerns until the responsible competent person has assessed and resolved them.
- The guide links were checked on 5 November 2026. Confirm the latest documents and applicable editions before design or installation.
References: Kattsafe installation requirements; competent review
Which ladder types are covered by the standard and this planner?
AS 1657:2018 separates step-type ladders, twin-stile rung ladders, single-stile rung ladders and individual-rung or step-iron ladders. Each has its own provisions. This planner illustrates the published Kattsafe twin-stile rung-ladder families only.
- Step-type ladders use different tread, angle and handrail provisions in Clause 7.3. They cannot be checked by relabelling a rung ladder.
- Single-stile ladders are addressed by Clause 7.5; step-irons by Clause 7.6. Their clearances, transitions and protection provisions must be assessed separately.
- Portable ladders and normal building evacuation or public-access stairs need their applicable requirements. The planning references here do not approve those uses.
References: AS 1657:2018, Section 2 & cls. 7.3–7.6
What is the maximum total height of a Kattsafe rung-ladder system?
The rung-ladder installation manual distinguishes the overall system height from the height between landing platforms: its system limitations state no overall height restriction, while limiting vertical distance between platforms to 6 m. Higher access therefore needs the appropriate multi-flight system and a verified design.
- RL20 is the mini angled family for roof-level access up to 3.5 m. RL30, RL40 and RL50 are published 6 m access references, with the matching intermediate platforms and components for greater total heights.
- Overall height still affects structural supports, wind loading, fall protection, access frequency and rescue. An absence of an overall height cap does not verify a particular installation.
- The 30 m input limit on this page is a software planning boundary, not a height limit or approval in a standard or product manual.
References: Kattsafe Rung Ladders Installation Manual, pp. 5 & 10, items 13–14
What is the key difference between a cage and a fall-arrest line?
A cage surrounds the climbing route and is a physical enclosure. It is not a fall-arrest device. A vertical fall-arrest system uses a compatible guided device, connection and harness to arrest a fall, subject to the system's clearance, structural and operating requirements.
- A caged ladder does not by itself provide a harness connection or a rescue system. The potential fall, actual cage geometry and local workplace requirements still need assessment.
- A vertical line needs the specified arrester and harness, correct installation, user competency, safe transfer, inspection and a practicable rescue method. A cable by itself is not a complete fall-arrest system.
- Both arrangements retain their applicable landing and product limits. Choose the complete documented system for the site and use, rather than treating cages and lines as interchangeable accessories.
References: AS 1657:2018, cl. 7.4.7 & Appendix H; Kattsafe SL228 installation manual
Kattsafe SL228 vertical fall-arrest guide (PDF) · AS 1657:2018 — publisher and full standard
Can a horizontal static line be used as the ladder's vertical fall-arrest line?
Do not substitute a general static line or horizontal lifeline for a documented vertical ladder fall-arrest system. The orientation, device, connections, supports and clearances must match the equipment's specified use.
- The RL50 reference uses its matching vertical fall-arrest arrangement. Follow the exact ladder and SL228 installation instructions, including compatible equipment and the system's limits.
- An independent roof protection system may also be needed for transfer and work beyond the ladder. That system needs its own design and safe connection method.
- AS/NZS 1891.4:2025 addresses selection, use and maintenance of personal equipment for work at height. The relevant equipment standards and manufacturer's instructions must also be identified.
References: Kattsafe vertical fall-arrest installation manual; AS/NZS 1891.4:2025 overview
Kattsafe SL228 vertical fall-arrest guide (PDF) · Standards Australia — AS/NZS 1891.4:2025
Is potential fall distance the same as the ladder height?
Not necessarily. A person may fall past the ladder base or a lower landing to another level. Clause 7.4.7 Note 1 calls for that continuing fall to be considered when determining potential fall distance.
- Measure and assess the full fall path, surrounding edges, openings and lower levels. Do not automatically use the height of one flight as the potential fall distance.
- Enter an assessed value in the planner if available. Leaving it blank keeps fall-protection selection as an open review item.
- A landing changes the fall path only when its actual position, dimensions and protection perform that function. The schematic cannot establish this for a site.
References: AS 1657:2018, cl. 7.4.7 Note 1 & Appendix H
Why is there a 4.5 m planning option for steep ladders?
Appendix H is informative. Its Table H1 includes 4.5 m maximum vertical landing-spacing guidance for rung ladders in the 75°–90° category. This is distinct from the normal 6 m requirement in Clause 7.3.6, applied through Clause 7.4.6.
- The planner starts vertical references with 4.5 m spacing so closer-flight planning is visible. Selecting 6 m does not confirm that a particular vertical arrangement is acceptable.
- Check the full table, potential fall category, manufacturer instructions and governing project requirements. Guidance may also be adopted as a binding project condition.
- The chosen interval divides the reference arrangement only; it does not assess every fall-protection, clearance or structural requirement.
References: AS 1657:2018, Appendix H / Table H1; cls. 7.3.6 & 7.4.6
Where should a ladder cage start and finish?
Clause 7.4.7 sets cage geometry as well as the circumstances requiring a cage. Its bottom termination is between 2000 mm and 2200 mm above the ladder base; its top extends at least 1000 mm above the platform landing or to the guardrail height where provided.
- The clause also controls internal dimensions, openings, projections, hoops, connections and protection at adjacent platform guardrails. Start and finish height alone are not a complete cage check.
- Use the matching Kattsafe cage assembly and current installation drawing. Do not fabricate a cage from the symbolic hoops shown in this planner.
- The drawing is not to scale and does not set installation clearances, cage dimensions or fixing positions.
References: AS 1657:2018, cl. 7.4.7; Kattsafe RL424 cage installation manual
Kattsafe RL424 cage installation guide (PDF) · AS 1657:2018 — publisher and full standard
Does a small footrest count as an intermediate landing?
A rung, footrest or small standing accessory is not automatically a landing. A landing used to satisfy the landing provisions needs the required dimensions, structural performance, surface, guarding, access and fall-path arrangement.
- Check the component's intended function and the complete manufacturer configuration. A product called a rest accessory should not be assumed to satisfy Clause 7.3.6.
- A top access platform, an intermediate change-of-direction landing and an existing suitable building floor can perform different roles in a design.
- The dimensional checker compares four entered values only. It does not assess surface strength, guarding, slip resistance or how the landing prevents a continuing fall.
References: AS 1657:2018, cl. 7.3.6 & Section 4; Kattsafe midway platform reference
Kattsafe midway landing platform specification · AS 1657:2018 — publisher and full standard
What is required at a step-through or side-access exit?
Use the appropriate exit type in Clause 7.4.8. For step-through access, the stiles extend at least 1000 mm above the top landing. Side access has its own stile/rung extension and transfer-gap provisions.
- For step-through access, Clause 7.4.8.1 specifies a 525–675 mm clear opening between the extended stiles, with strength, deflection and hand-clearance requirements.
- For side access, Clause 7.4.8.2 specifies stile and rung extension at least 1000 mm above the landing and a horizontal stile-to-landing gap of 90–175 mm. Review the complete surrounding guarding and safe-transfer detail.
- These are different layouts. The planner does not add a generic head-extension length to manufacture a ladder or certify its exit geometry.
References: AS 1657:2018, cls. 7.4.8.1 & 7.4.8.2
How should access through a roof hatch be arranged?
Clause 7.4.8.3 provides the requirements for horizontal openings. It addresses extended stiles or handrails, or handgrips above the opening, and how the hatch and any extendable handholds can be operated safely.
- Where opening or extending components must be done from the ladder, the clause addresses remote or one-handed operation, or a platform in the stated circumstances. Review the exact arrangement rather than assuming every hatch needs the same component.
- Check the opening, clearances, guarding, safe route beyond it and the manufacturer's matching system. Appendix J adds informative roof-access guidance.
- A hatch context in the illustration is a prompt for design review. It is not a dimensioned hatch installation detail.
Documented alternatives for horizontal openings: Clause 7.4.8.3 allows the stated extended stile/handrail or above-opening handgrip approaches, with conditions for opening the hatch and extending handholds. Select the matching complete arrangement; a handgrip is not a general substitute for every top-landing and access requirement.
References: AS 1657:2018, cl. 7.4.8.3 & Appendix J
Can the ladder land directly on a sloping roof?
Assess the bottom and top separately. Clause 7.4.3.5 permits a limited bottom-landing cross-slope up to 7° total, subject to the required rung relationship. Clause 7.4.8.4 limits the top landing slope to 3° in any direction.
- The bottom cross-slope provision does not allow a generally sloping top landing or remove landing dimensions, clearances, structural and fall-protection requirements.
- Kattsafe's manual calls for base/top landings where entry or exit is uneven or not level. Use the exact product detail, with written consent for a departure from the installation guide.
- A separate level platform may therefore be needed for a pitched roof, parapet or uneven surface. A suitable existing surface can serve as the landing when all applicable conditions are met.
Limited geometric allowance — bottom landing only: The 7° total cross-slope allowance is specific to the bottom landing and its rung relationship. It does not replace the 3° top-landing limit or the exact product's requirements. If the manufacturer detail needs a level platform, provide that detail or obtain its required written consent for a different arrangement.
References: AS 1657:2018, cls. 7.4.3.5 & 7.4.8.4; Kattsafe manual p. 10
Kattsafe rung-ladder installation manual (PDF) · AS 1657:2018 — publisher and full standard
Does fitting fall arrest change the support and fixing design?
Yes. Arresting a fall introduces forces that must be verified for the complete ladder, supports, anchors and structure. A caged ladder's fixing arrangement must not be assumed suitable for a retrofit vertical fall-arrest line.
- AS 1657 Clause 7.1.2 addresses design loads; Clause 7.4.4 addresses ladder fastenings. Appendix H also discusses fall-arrest forces and clearances as informative guidance.
- Kattsafe's system limitations specify different support requirements for caged and vertical fall-arrest systems. Obtain the current product loads and exact detail for structural verification.
- The planner does not calculate bracket spacing, anchor capacity, cable tension, torque or fall clearance. These need the relevant product and engineering information.
References: AS 1657:2018, cls. 7.1.2 & 7.4.4; Kattsafe manual p. 10
Kattsafe rung-ladder installation manual (PDF) · AS 1657:2018 — publisher and full standard
Can fall arrest be added to an existing or suspended ladder?
Only after the exact ladder and support arrangement have been assessed as suitable. Kattsafe's manual says a suspended ladder is unsuitable for a fall-arrest device unless it is specifically designed and fabricated for that use.
- Check the original manufacturer, ladder condition, structure, fixing loads, compatibility, transfer and rescue arrangements before changing an existing installation.
- Obtain written manufacturer consent for departures from the guide. Retrofitting a cable alone does not establish a verified system.
- Suspended/custom configurations are outside this planner's illustrations. Obtain their specific drawings and required engineering verification.
References: Kattsafe Rung Ladders Installation Manual, p. 9 & p. 10 items 23–24
Who should install the system, and what needs inspection?
Kattsafe's installation requirements call for authorised and accredited installers with appropriate training and industry licences. The installation and its supporting structure need competent assessment, followed by the specified handover, inspection and maintenance arrangements.
- Use the current manual for the exact product. A generic trade qualification or the planner's evidence log does not establish manufacturer authorisation.
- The rung-ladder manual recommends recertification at 12 months in a mild/non-corrosive environment and 6 months in a harsh/corrosive environment, with more frequent inspection where needed. These are manufacturer recommendations for that system, not a universal statutory interval for all ladders.
- Equipment subjected to abnormal loading or showing defects needs withdrawal from use and competent assessment in accordance with the manufacturer's instructions.
References: Kattsafe Rung Ladders Installation Manual, pp. 9–10; AS/NZS 1891.4:2025
Kattsafe rung-ladder installation manual (PDF) · Standards Australia — AS/NZS 1891.4:2025
What should a useful design and handover brief contain?
Record the access task, measured site geometry, selected state, governing standard edition, exact product drawings, structure, fall path, landing layout, protection system and rescue arrangements. Record the responsible people and the required verification and acceptance.
- AS 1657 Section 8 addresses labelling and documentation. Kattsafe's installation requirements also address the handover and operating information.
- Keep calculations, structural verification, installation records, inspection findings, operating limits and maintenance requirements with the completed system as applicable.
- The downloadable brief helps identify open evidence. A recorded item is user-entered and unverified; it does not issue a certificate or close a design departure.
References: AS 1657:2018, Section 8; Kattsafe installation requirements p. 9
Kattsafe rung-ladder installation manual (PDF) · AS 1657:2018 — publisher and full standard
Does choosing another state change the landing dimensions?
The AS 1657 reference dimensions and flight calculations in this planner are the same for every state and territory. Selecting the worksite location changes the linked workplace regulator guidance and the location recorded in the review brief.
- NSW is selected by default and needs confirmation or a change to the actual worksite state. Local workplace law, applicable codes and the project specification must still be checked.
- A regulator's provision for a different method of meeting a code does not automatically waive a binding standard, contract or manufacturer limit.
- Confirm the governing edition and any project conditions with the responsible designer or reviewer. The state selector does not approve an exception.
References: AS 1657:2018; selected state/territory regulator guidance; project specification
How should I read a standard and establish what is legally binding?
Start with the applicable law, workplace code, contract and asset specification, then identify the standard edition and product instructions they require. A current publication and the edition governing a particular project are not automatically the same thing. Standards Australia explains that its standards are voluntary unless given mandatory effect, including through legislation.
- Read the scope and exclusions before applying a numerical clause. Check the definitions, linked clauses, normative references, figures, amendments and the document's conventions. A sentence taken from a search result is not a complete requirement.
- Within AS 1657, distinguish requirements from recommendations, informative appendices and commentary. Its preface specifically makes mandatory statements in notes to figures requirements; this is why a blanket statement that all notes are optional would be wrong.
- Read legislation and approved codes in their own legal context. SafeWork NSW explains the code duty applying from 1 July 2026 and the equivalent-or-higher alternative for managing a code risk. That does not create a general waiver of a prescribed ladder clause, a contract requirement or a product limit.
- Record the governing documents, the exact design route and the evidence for each condition. Resolve uncertainty with the responsible competent designer and relevant regulator or authority before relying on a departure. The planner is a reference aid and cannot make that legal determination.
References: AS 1657:2018, preface, scope & referenced clauses; Standards Australia FAQs; SafeWork NSW codes guidance
SafeWork NSW — current code duty and terminology · AS 1657:2018 — publisher and full standard · Standards Australia — standards status and access
Does meeting a minimum dimension mean the design complies?
A numerical minimum is one part of a requirement. Meeting it does not establish that every applicable load, clearance, surface, guarding, access, protection, installation and operating condition has been satisfied. The completed system must be assessed as a whole.
- For example, the landing checker compares length, width, headroom and standing space. It does not verify top slope, surface strength, slip resistance, guarding, adjacent hazards or the fall path between flights.
- An expressly permitted option within a clause is different from a departure. To use an option, satisfy all of its qualifying conditions. Where those conditions are not met, do not describe the arrangement as complying with that option.
- Manufacturer consent to a product departure does not by itself waive a statutory or contractual requirement. An engineering calculation also needs to address the governing design basis and cannot simply erase a mandatory provision.
- Use the green result only as a comparison of the entered number with the stated reference. A competent assessment, required records and acceptance remain necessary before certification or use.
References: AS 1657:2018, Sections 3, 4, 7 & 8; Kattsafe manual p. 9
How far apart should rungs be, and what happens at the first and last rung?
Clause 7.4.3.2 specifies rung spacing for twin-stile rung ladders. For ladders longer than 1 m it is 250–300 mm; for ladders up to 1 m, rungs are evenly spaced at no more than 300 mm. The standard also specifies uniformity and tolerances. Kattsafe publishes a 300 mm pitch for the reference families here.
- Pitch is measured along the ladder, not by multiplying a vertical rise by the number of rungs. The angle changes the vertical rise achieved at each rung.
- Clause 7.4.3.3 places the top rung at the top landing height. Clause 7.4.3.4 sets the bottom rung-to-landing distance at 90–100% of the rung pitch. These are specific end relationships, not permission to vary all the rungs.
- Do not accumulate manufacturing tolerances to obtain a different flight height. Use the complete manufacturer head/body/base detail and verify the actual first and last rung positions.
- The planner displays an approximate count of rung spaces only. It does not establish the final rung count, total ladder length or cut and fixing schedule.
References: AS 1657:2018, cls. 7.4.3.2–7.4.3.5; Kattsafe rung-ladder specifications
What clear space is needed around a fixed rung ladder?
Clause 7.4.5 sets clearances to permanent objects outside the ladder installation. These include at least 200 mm behind the back edge of the rung, 750 mm in front measured perpendicular to the ladder from the rung nosing, and the stated side and hand-clearance provisions.
- The side provision includes 350 mm from the ladder centre-line with its specified geometric qualification. Stile hand clearance is at least 50 mm. Use the full clause and Figure 7.7 when measuring, rather than adding a generic width around the drawing.
- For a caged ladder, the front and side dimensions are modified by the cage requirements in Clause 7.4.7. Assess the internal cage geometry and nearby platform guarding together.
- A vertical ladder having zero calculated horizontal projection still occupies physical space and needs clearances for climbing, transfers and rescue. Projection is not an installation footprint.
References: AS 1657:2018, cls. 7.4.5 & 7.4.7, Figures 7.7–7.9
What is the difference between clear stile width and overall ladder width?
The clear distance between stiles and the outside width of the ladder are different measurements. Clause 7.4.2.1 gives a clear stile range of 375–525 mm. Kattsafe's reference specification distinguishes 525 mm clear stile width from 605 mm overall width.
- The landing width provision in Clause 7.3.6 requires at least the ladder width or 600 mm, whichever is greater. The checker defaults to the reference ladder's 605 mm overall width; use the actual selected product width.
- An opening between extended stiles at a step-through head is a separate dimension under Clause 7.4.8.1. Do not substitute the body clear width or the cage width for that head opening.
- Confirm the drawing for the exact variant, including brackets, cage, roof interface and space outside the stiles. A catalogue width does not establish the complete installed footprint.
References: AS 1657:2018, cls. 7.4.2.1, 7.3.6 & 7.4.8.1; Kattsafe product specification
Kattsafe rung-ladder range and specifications · AS 1657:2018 — publisher and full standard
Can more than one person use the ladder, or carry heavy equipment on it?
Kattsafe's rung-ladder manual rates the referenced system for single-person use at 150 kg. Use the exact product's operating limitations and assess the person, carried equipment, task and rescue arrangements. Do not treat a ladder as a lifting point or general work platform.
- A separate fall-arrest device or line can have its own user, mass and connection limits. These must also be met; the ladder's rating alone does not approve the whole system.
- The manual prohibits using the system to tether or lift machinery or equipment. Plan a suitable means of transporting tools and materials while preserving safe climbing and connections.
- Frequent access, substantial tools or awkward loads may justify another access method under the access hierarchy. The planner does not approve a work task or lifting operation.
References: Kattsafe Rung Ladders Installation Manual, p. 10 items 2 & 9; AS 1657:2018 cl. 2.2
Kattsafe rung-ladder installation manual (PDF) · AS 1657:2018 — publisher and full standard
How do weather, corrosion and location affect the design?
The installation's environment affects material suitability, corrosion protection, fixings, wind loading, inspection and safe use. Kattsafe's system limitations address these matters and prohibit submerging the rung ladder in saline or acidic liquids.
- External installations need the relevant wind loads considered. Connections between dissimilar metals need the specified isolation measures and suitable protection.
- Corrosive or harsh conditions can require shorter inspection intervals and additional protection. Obtain the manufacturer's advice for the actual exposure rather than assuming an aluminium component is suitable everywhere.
- Wet, contaminated or damaged rungs and landing surfaces require appropriate controls and maintenance. The calculator does not evaluate environmental conditions or certify durability.
References: AS 1657:2018, cl. 3.3.3; Kattsafe manual p. 10 system limitations
Kattsafe rung-ladder installation manual (PDF) · AS 1657:2018 — publisher and full standard
Do I need a lockable gate or measures to prevent unauthorised climbing?
Assess who can reach the ladder and how access is controlled. Commentary C7.4.7 discusses preventing unauthorised access at publicly accessible locations, including a lockable cage entry and measures that discourage climbing outside the cage. Commentary is explanatory guidance, not an automatic universal gate requirement.
- Restricted or locked-off access also appears in the informative Appendix H guidance for relevant ladder categories. Determine the controls for the actual users and site.
- Use the compatible manufacturer access-control detail and assess the surrounding guarding and safe entry. A gate alone does not provide fall arrest or satisfy the landing provisions.
- Any access-control arrangement must be coordinated with the intended operation and emergency arrangements. The planner does not design security, egress or a rescue procedure.
References: AS 1657:2018, Commentary C7.4.7 & Appendix H; Kattsafe component drawings
What rescue arrangements are needed with ladder fall arrest?
Fall arrest can leave a person suspended or unable to recover themselves. The site needs a practicable rescue method, competent people, suitable equipment and effective emergency procedures. SafeWork NSW requires fall-arrest emergency and rescue procedures to be tested for effectiveness.
- Plan rescue for the actual ladder, landing levels, transfer points, casualty position and surrounding structure. Check how rescuers can access and recover the person without creating another uncontrolled fall risk.
- Kattsafe recommends that people using fall arrest do not work alone. A phone call or a generic emergency number is not evidence that the site's rescue method is workable.
- Use the equipment instructions, applicable work method and training requirements. This page can identify rescue as an open item but cannot design, demonstrate or certify a rescue system.
References: SafeWork NSW working-at-heights guidance; Kattsafe manual p. 10; AS/NZS 1891.4:2025
SafeWork NSW — working at heights · Standards Australia — AS/NZS 1891.4:2025
Why can a hire company offer an extension ladder longer than a fixed-ladder flight?
Portable extension ladders and permanently installed rung ladders are different equipment categories. AS 1657:2018 cl. 1.2(c) excludes temporary access, including portable ladders. Its fixed-ladder landing interval is therefore not a universal length rule for a portable hire ladder.
- For example, Kennards lists a 6.0–10.8 m extension ladder. That listing identifies a portable extension ladder, not a 10 m A-frame stepladder or approval of an unrestricted 10 m vertical climb.
- Check whether a quoted measurement is ladder length, maximum extension, platform/standing height or working reach. They are not interchangeable. The exact product label and instructions govern its extension, overlap, load and permitted standing positions.
- Portable ladders have their own AS 1892 requirements and task-specific risk controls. A hire listing alone does not establish suitability, remove fall risk duties or authorise attaching a harness to the ladder. Consider safer access and a protected working platform where appropriate.
- SafeWork NSW separates portable and fixed ladders in its falls code. This fixed-ladder calculator does not assess a portable ladder or certify a hire arrangement. No portable-ladder maximum is inferred from the fixed-ladder thresholds shown here.
References: AS 1657:2018, cl. 1.2(c); SafeWork NSW falls code, ss. 9.1–9.2; AS 1892 series
SafeWork NSW — falls code, portable/fixed ladders · AS 1657:2018 — publisher and full standard · Kennards — portable extension ladder hire range
What is the maximum distance between fixed-ladder support brackets?
Bracket spacing is a product and configuration requirement, separate from landing spacing. Kattsafe's general rung-ladder instructions state a 3,000 mm maximum between support brackets, but the vertical-line detail on p. 15 specifies a closer 2,800 mm maximum. Use the exact applicable drawing; do not apply the general figure to every ladder.
- The p. 15 details show a top bracket within the top 600 mm, subject to their specific platform-kit alternative. Follow the drawing's measurement points and support arrangement.
- The RL413 stile-strengthening kit is required where the guide permits bracket spacing beyond 3,000 mm. This is not permission for any unsupported span: obtain the manufacturer's exact strengthened arrangement, loads and fixing details.
- Suspended and fall-arrest ladders have separate, more demanding support conditions. Confirm reactions, substrate, wind exposure, fasteners and structural adequacy with the manufacturer and competent designer.
- Adding brackets does not replace intermediate landings, a cage, a ladder line, guarding or rescue arrangements. This page does not size a support, anchor or fixing.
References: Kattsafe rung-ladder installation manual, pp. 10, 13–15
Can a fixed ladder hang from the structure without support at ground level?
Kattsafe documents suspended ladder arrangements using the designated suspension brackets. They must be selected as a complete suspended system; an ordinary supported ladder cannot simply have its base support removed.
- The suspended caged detail identifies at least two designated brackets for a ladder up to 6 m. The guide also gives bracket reactions and spacing conditions; bracket count alone does not prove the design.
- For the suspended vertical fall-arrest arrangement, the guide identifies at least four brackets per 6 m ladder or a maximum 2,400 mm spacing. Read the complete technical notes and drawing together and obtain confirmation of the exact arrangement.
- The manual expressly says a suspended ladder is unsuitable for a fall-arrest device unless specifically designed and fabricated for it. Dynamic arrest loads and connection to the supporting structure are critical.
- Suspension is a support method, not an exception to the landing interval. Obtain the exact manufacturer's installation detail and structural verification; do not improvise a suspended line system from this illustration.
References: Kattsafe rung-ladder installation manual, pp. 10, 13–14
Can a landing platform replace the top fixing bracket?
Only the specific documented arrangement should be relied on. Kattsafe's p. 15 detail allows the top bracket to be omitted when the RL432A platform walkway kit is used and the platform is bolted to the ladder stile.
- This is a named component and connection condition, not permission to omit a bracket whenever a roof or platform happens to touch a ladder.
- Where the vertical detail omits that bracket, the guide says to measure spacing from the landing to the next bracket below. All other applicable support, fixing and structural conditions remain.
- Confirm the current drawing with Kattsafe for the selected ladder family and load case. An alternative platform, suspended arrangement or modified connection needs its own documented acceptance.
References: Kattsafe rung-ladder installation manual, p. 15
How high can a portable ladder access bracket be used?
A portable-ladder support bracket stabilises a compatible portable ladder at an access point; it does not turn it into an approved fixed-ladder installation. Kattsafe recommends that its RL401/RL402 support bracket is not used above 4,000 mm because of portable-ladder instability at greater heights.
- That is a manufacturer recommendation for this product, not a universal statutory maximum for every portable ladder. Do not treat a longer hire ladder as approval to exceed the bracket's documented guidance.
- The guide requires a firm support surface and footing, suitable loading and a ladder extending at least 1,000 mm above the roof, parapet or wall for exit. It also addresses tie-off, access positioning and transition protection.
- The bracket is not automatically a personal fall-arrest anchor. Any anchor or connecting strop must be a separately suitable system with a safe transfer procedure, appropriate equipment and rescue arrangements.
- Ask the manufacturer for the correct access design where the height, roof or support differs. Consider permanent access, stairs, scaffold or another suitable access method rather than assuming a bracket permits the arrangement.
References: Kattsafe RL401/RL402 support-bracket manual, pp. 8–9
Do tile, sheet-metal, parapet and flat roofs need different bracket details?
Yes: the attachment must be documented for the actual substrate, profile, supporting structure and selected product. A roof's name or appearance does not establish that a fixing is suitable. A portable access bracket and a bracket supporting a permanent rung ladder perform different roles.
- Sheet-metal roofs need the manufacturer's specific profile, material/thickness, fixing and supporting-structure conditions. Do not substitute a roof-sheet fixing for a structural ladder-support detail.
- For tiled roofs, obtain a manufacturer detail expressly covering the tiles and underlying structure. The illustrated RL401/RL402 details do not establish a generic tiled-roof fixing. Do not assume that fastening to a tile or gutter alone provides an approved support.
- On flat roofs, check structure, membrane/weatherproofing, drainage, safe approach and the guarded route beyond the access point. Flat does not necessarily mean level, load-bearing or safe to walk on.
- Parapet/wall mounting needs the matching bracket, substrate and connection detail. Check the step-off, handholds, fall edge and protective measures, as well as preventing ladder movement. For pitched or uneven surfaces, check the required level landing arrangement.
References: Kattsafe RL401/RL402 support-bracket manual, pp. 5, 7–12; rung-ladder manual, pp. 9–10
How often should ladders and access brackets be inspected?
Distinguish a pre-use condition check from a scheduled competent inspection. SafeWork NSW advises inspecting a portable ladder for damage before each use. For the Kattsafe systems covered by the linked guides, the manufacturer specifies competent inspection and recertification at 12 months in non-corrosive conditions or 6 months in corrosive/harsh conditions, with the environment assessed by a competent person.
- Do not apply those product intervals to every ladder, harness or anchor. The exact equipment manual, governing standard, environment, usage and any stricter asset requirements determine the inspection schedule.
- Review the structure, connections, fixings, stiles/rungs, cage or line, landings, guarding, access controls and readable identification. Personal fall-arrest components also need their own equipment-specific checks.
- Damage, distortion, corrosion, an abnormal load or a fall event calls for the relevant stop-use and assessment procedure; a future inspection due date is not permission to continue using defective equipment.
- Keep inspection findings, defects, corrective actions, the inspector's details and next due date with the asset record. A user completing this calculator's checklist is not an independent inspection or recertification.
References: Kattsafe rung-ladder manual, pp. 45–46; support-bracket manual, pp. 13–14; SafeWork NSW ladder guidance
Kattsafe rung-ladder installation manual (PDF) · SafeWork NSW — ladder safety · Kattsafe portable-ladder support-bracket manual
What signage, labels and inspection tags should be provided?
Use the identification and operating information specified for the complete system and the site. Kattsafe's guides require completed identification/recertification information and documented maintenance; their inspection checklists call for visible, legible instruction labels and updated current/next inspection dates.
- Record asset identification, system instructions, relevant use restrictions, inspection status and the supporting report. Where harness-based fall arrest is required, make the equipment, connection, training and rescue instructions available before access.
- Non-conforming equipment must be clearly identified and tagged 'Do Not Use' until a competent person completes the corrective action. A green sticker or QR code alone does not prove the design, installation or current condition is compliant.
- Access-control gates or ladder doors can manage unauthorised access but do not replace guarding, safe transitions or rescue. Use the exact documented door/gate assembly.
- The page does not prescribe a universal tag colour, sign wording or inspection interval under AS 1657. Confirm the actual product and asset requirements; keep the manufacturer's full instructions accessible.
References: Kattsafe rung-ladder manual, pp. 42, 45–46; support-bracket manual, pp. 13–14
Kattsafe rung-ladder installation manual (PDF) · Kattsafe portable-ladder support-bracket manual
Do towers, wind turbines, pits or special structures have an automatic landing exemption?
No automatic exemption follows from the structure's name. AS 1657 cl. 1.1 Note 1 discusses guidance for certain machinery, towers, wind-turbine towers and water/sewerage facilities where no directly applicable standard exists. Clause 7.3.6 Note 3 separately addresses intermediate landings that are not reasonably practicable and recommends an AS/NZS 1891-series fall-arrest system.
- First identify any directly applicable machinery, turbine, industry or asset standard and the governing law/specification. The scope note does not displace a directly applicable standard or waive structural principles and imposed actions.
- Note 3 names examples such as lighting/transmission towers, wind-turbine towers and pits. It provides no replacement numeric maximum and does not establish permission for an unlimited or cage-only uninterrupted climb.
- For a proposed alternative, document why intermediate landings are not reasonably practicable, safer access options, the full fall path, fatigue/access needs, structural and arrest loads, compatible equipment, safe transfer, rescue and the necessary design/asset/manufacturer acceptance.
- Kattsafe's standard rung-ladder guide still states a 6 m maximum between platforms. A special turbine or tower design must be separately documented and accepted; this calculator cannot approve it or generate a certified special-purpose ladder.
References: AS 1657:2018, cl. 1.1 Note 1; cl. 7.3.6 Note 3; Kattsafe manual, pp. 9–10
What evidence would a designer need for a longer custom access arrangement?
Start with measured information and the governing requirements, not a requested height alone. The designer needs to determine whether a normal multi-flight ladder, another access method or a specifically permitted and accepted alternative is appropriate.
- Provide total rise, individual flight levels, inclination, full potential fall path, access frequency, users, carried equipment, available landing space and the reason a normal arrangement may be impracticable.
- Include drawings/photos of the structure, roof and substrate, available support points, transitions, edge/opening hazards and environmental exposure. Record the applicable standard editions and asset specification.
- For a proposed fall-arrest alternative, include the exact compatible manufacturer system, connection procedure, clearance assessment, structural load verification, training, inspection and practicable rescue arrangements.
- The outcome must state what requirements are met, what permitted alternative is relied on and any unresolved departure. Manufacturer consent or an engineering opinion does not by itself waive a binding legal or contractual requirement. There is no automatic approval from a calculator, AI answer or signed checklist.
References: AS 1657:2018, cl. 7.3.6 Note 3; Kattsafe installation requirements